rack mounted servers racks transfer switch ups1

Location of Server: Lansing, Michigan
Datacenter: Liquidweb
Hardware Pentium: 4 2.8 HT with 2 Virtual Processor

Robust Electrical System Including:
» Incoming commercial power service routed underground to a dedicated transformer
» 300 kVA Powerware 9315 centralized UPS with redundant battery cabinets
» Over 4 hours of UPS runtime on battery backup at current load
» 313 kVA standby Cummins diesel generator (Automatically activated by transfer switch)
» Over 24 hours of runtime on generator before requiring additional fuel at full load
» Liebert Precision power distribution unit
» UPS full maintenance bypass allows for power upgrades and UPS service without interruption of power to equipment

Security:
» Complete network IDS (Intrusion Detection System) monitors data and network security transparently through an optical tap
» Closed circuit security camera system covering all building and data center entrances along with integrated motion detection systems
» Six to eight weeks of security data is retained at all times
» Access to facility is restricted to technical staff employees